F30600

SI P2: STOP A initiated

Siemens · SINAMICS G120C Variable Speed Drive

What does F30600 mean?

The drive-integrated "Safety Integrated" function on processor 2 has detected an error and initiated a STOP A. This is often caused by an unsuccessful forced checking procedure of the safety shutdown path or as a consequence of F30611. This fault indicates a critical issue within the safety system, preventing drive operation and requiring immediate resolution to maintain machine and personnel safety.

Complete Troubleshooting Guide

  1. 1

    Activate and then deactivate the Safe Torque Off (STO) function.

  2. 2

    Perform a complete power cycle (POWER ON) for all involved drive components.

  3. 3

    If the fault persists, replace the Power Module.

  4. 4

    If fault value is 9999, diagnose and resolve fault F30611.