F30903
Power unit: I2C bus error occurred
Siemens · SINAMICS G120C Variable Speed Drive
What does F30903 mean?
This fault signifies a communication error on the I2C bus, typically with an EEPROM or an A/D converter within the power unit. The fault value (r0949) provides specific detail: 80000000 hex indicates an internal software error, while 00000001-0000FFFF hex points to a module fault. This can lead to incorrect readings, configuration issues, or unreliable operation. The risk is complete or partial failure of the affected module.
Complete Troubleshooting Guide
- 1
If the fault value is 80000000 hex, upgrade the power unit firmware to a later version to address potential software bugs.
- 2
If the fault value is between 00000001 hex and 0000FFFF hex, replace the specific faulty module indicated by the fault value.