A35415
TM150 Temperature Alarm Channel 9
Siemens · SINAMICS S120/S150 List
What does A35415 mean?
This alarm is initiated when the actual temperature (r4105[9]) for channel 9 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[18]). A timer (p4103[9]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[9]).
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check for any immediate causes of temperature increase for the affected component, such as temporary overloads or environmental factors.
- 4
Verify the temperature sensor operation and connection for channel 9.
- 5
Review the alarm threshold setting (p4102[18]) and hysteresis (p4118[9]) to ensure they are appropriate for the application.
Source: Siemens SINAMICS S120/S150 List