Infeed: Line phase failure
Siemens · SINUMERIK 828D CNC Control
What does 206200 mean?
One or several line phases have failed, or an overvoltage condition has persisted, causing the infeed to fault. This can occur during power-on if the PLL cannot synchronize due to incorrect phase assignment (e.g., with a VSM) or during operation after a significant voltage dip or overvoltage. Alarm A06205 usually precedes this fault, providing additional diagnostic information.
Complete Troubleshooting Guide
- 1
Inspect the incoming line supply for physical phase loss, significant voltage dips, or overvoltages that last longer than 10 ms.
- 2
Verify the correct phase assignment (L1, L2, L3) at the Voltage Sensing Module (VSM) and ensure it matches the assignment at the power unit.
- 3
Check for an overload condition on the load side that could cause peak currents, potentially leading to this fault condition.
- 4
Ensure the commutating reactor is present, correctly installed, and properly functioning, as its absence can contribute to this issue.
- 5
Refer to Alarm A06205 if it was triggered, as its warning value can provide crucial information regarding the cause of the line supply fault.