3501
Insulation monitoring device detected low grounding resistance
SMA · SUNNY CENTRAL 500CP XT / 630CP XT Solar Inverter
What does 3501 mean?
The insulation monitoring device has measured a grounding resistance value that is too low. This indicates a potential ground fault within the PV array, which can pose a safety risk and reduce system performance. The inverter will switch to the 'Disturbance' operating state.
Common Causes
- Ground fault in the PV array.
- Degraded insulation in PV modules or wiring.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Perform an insulation resistance test on the PV array to identify the location of the ground fault.
Verified technical data. Last updated: March 2026