101
PID Feedback Supervision Fault (PID1)
Vacon · 100 FLOW Application
What does 101 mean?
The feedback value for PID controller 1 is outside the configured supervision limits (P3.13.6.2 and P3.13.6.3) for a specified delay (P3.13.6.4). This indicates a deviation from the expected process variable feedback, suggesting an issue with the process or the sensor. It can lead to incorrect control actions and process instability.
Complete Troubleshooting Guide
- 1
Investigate the process being controlled for any anomalies or deviations in the feedback loop.
- 2
Check the PID controller parameter settings, specifically the supervision limits (P3.13.6.2, P3.13.6.3) and the delay (P3.13.6.4) for correctness.
- 3
Verify the integrity and calibration of the feedback sensor connected to PID1.