AC Drive Board Overtemperature Fault
Vacon · 100 FLOW Application
What does 132 mean?
The temperature on the AC drive's power board has exceeded its safe operating limit, indicating a critical overheating condition. This fault is typically caused by insufficient cooling air, high ambient temperatures, or internal component issues. Sustained high temperatures on the board can lead to permanent damage to sensitive electronic components.
Complete Troubleshooting Guide
- 1
Verify the quantity and flow of cooling air to the drive and ensure internal components are not obstructed.
- 2
Check the ambient temperature to ensure it is within the drive's specified operating limits.
- 3
Inspect the cooling fan for proper operation and any obstructions.
- 4
Review the drive's parameter settings, especially the switching frequency, in relation to the ambient temperature and motor load.