3
Earth Fault
Vacon · 100 FLOW Application
What does 3 mean?
The sum of the motor phase currents is not zero, indicating a current leakage to earth, detected by either hardware or software. This is typically caused by insulation malfunction in the motor or its cables, or a malfunction in associated filters (e.g., du/dt, sinus filters). An earth fault poses a safety risk and can cause equipment damage.
Complete Troubleshooting Guide
- 1
Perform an insulation resistance test on the motor and its cables.
- 2
Check any installed du/dt or sinus filters for proper operation and integrity.