32

Fan Cooling Fault

Vacon · 100 FLOW Application

What does 32 mean?

This fault indicates an issue with the cooling fan, either its speed does not accurately match the reference (for MR7 and larger drives) or its estimated lifetime (50,000 h) has expired. Inadequate cooling can lead to drive overheating, reduced performance, and eventual damage.

Complete Troubleshooting Guide

  1. 1

    For fan speed issues (ID 311), reset the fault and restart the drive. Clean or replace the fan if necessary.

  2. 2

    For fan lifetime expiry (ID 312), replace the cooling fan.

  3. 3

    After fan replacement, reset the fan lifetime counter in the drive's parameters.