Undervoltage

Vacon · NX Liquid-Cooled Drive

What does 9 mean?

The DC-link voltage has decreased below the predefined limits. This is most often caused by an insufficient supply voltage, a component failure within the drive, a defective input fuse, or an external charge switch that is not properly closed. For 400-500Vac mains, a fault trips at 333Vdc (warning at 371Vdc); for 500-690Vac mains, a fault trips at 573Vdc (warning at 633Vdc). Subcodes S1 (DC-link too low during run), S2 (no data from power unit), and S3 (undervoltage control supervision) are available.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check all input fuses for continuity and proper rating.

  2. 4

    Ensure any external charge switch is in the closed position.