14
Frequency converter overtemperature
Vacon · NXP/C AC Drive
What does 14 mean?
The heatsink temperature of the frequency converter has exceeded 90 °C (a warning is issued at 85 °C). Subcodes in T.14 indicate the measurement source (S1 = Measurement, S2 = Internal thermistor). Prolonged operation at high temperatures can cause irreversible damage to the drive's internal components.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Measure the ambient temperature surrounding the frequency converter; ensure it is within the specified operating limits.
- 4
Review parameter settings for switching frequency; reduce it if found to be too high in relation to the ambient temperature and motor load.
Source: Vacon NXP/C AC Drive
Open Manual (Page 107)