9
Undervoltage
Vacon · NXS NXP AC Drive
What does 9 mean?
The DC-link voltage has fallen below its defined limits. This is most commonly caused by a low supply voltage, a temporary supply voltage break, a defect in an input fuse, or an external charge switch not being closed. Persistent undervoltage can cause erratic drive behavior or prevent it from starting.
Complete Troubleshooting Guide
- 1
In case of a temporary supply voltage break, reset the fault and restart the frequency converter.
- 2
Check the main supply voltage to ensure it is within specified limits.
- 3
Inspect input fuses for continuity and proper rating.
- 4
Verify the state of any external charge switches.
- 5
If supply voltage is adequate and the problem persists, an internal failure may have occurred – contact the distributor.