15
Motor stalled
Vacon · NXS NXP Drive
What does 15 mean?
The motor has stalled, meaning it is not rotating despite receiving a run command. This is typically due to an excessive mechanical load or an obstruction preventing rotation. A stalled motor will draw very high current, leading to rapid overheating of the motor windings and potentially the drive's output stage.
Complete Troubleshooting Guide
- 1
Inspect the motor and its connected load for any mechanical obstructions, binding, or excessive friction.
- 2
Verify that the motor is not overloaded beyond its rated capacity.
- 3
Ensure the application's torque requirements are within the capabilities of both the motor and the drive.