BUS-LED 3-1

Insufficient configuration data (Fault code 3, argument 1)

Wago · Modular I/O System PROFIBUS DP

What does BUS-LED 3-1 mean?

The Fieldbus Coupler has insufficient configuration data, most likely because an I/O module was overlooked during the configuration process. This prevents the coupler from fully recognizing and operating all connected modules, leading to incomplete system functionality.

Common Causes

  • A specific I/O module was omitted from the configuration
  • The loaded configuration data is incomplete for the physically connected modules

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the configuration to verify all physical modules are included.

  2. 2

    Load the corrected configuration onto the coupler.

  3. 3

    Cycle the supply voltage of the coupler (off then on again) to restart.

Browse all codes in this manual (21)
Verified technical data. Last updated: March 2026

Related Faults