Fan Failure Overheat 1
Yaskawa · E7 Drive
What does OH1 mean?
An OH1 fault signals an overheat condition specifically caused by the failure or malfunction of the drive's internal cooling fan. When L8-32 is enabled, this fault will occur, indicating that the drive's ability to dissipate heat is compromised. Prolonged operation without adequate cooling will inevitably lead to damage of internal power components and system shutdown.
Complete Troubleshooting Guide
- 1
Visually inspect the internal cooling fan for any physical damage, obstructions, or whether it is spinning when the drive is powered.
- 2
Clean any dust, debris, or foreign objects from the fan blades and heatsink areas.
- 3
If the fan is not operating, check its electrical connections. If necessary, replace the cooling fan unit.
- 4
Confirm that parameter L8-32 (OH1 Detection Selection for Fan Failure) is enabled to ensure this critical protection is active.