UV
Undervoltage Alarm
Yaskawa · E7 Drive
What does UV mean?
This is a warning displayed on the digital operator during a momentary power loss event. It indicates that incoming AC power has been interrupted, but the drive's control power supply is still being maintained. The alarm signifies the drive is in a ride-thru state and will precede a UV1 fault if power is not restored within the configured ride-thru time (L2-02).
Complete Troubleshooting Guide
- 1
Monitor the incoming AC power supply for fluctuations or temporary interruptions.
- 2
Verify that the power loss ride-thru settings (L2-01, L2-02) are configured as desired for your application's requirements.
- 3
Check for loose connections in the AC input power circuit to ensure stable and continuous power delivery to the drive.