CPF22

Option Board Code Number Fault

Yaskawa · F7 Drive

What does CPF22 mean?

An unrecognizable option board was connected to the control board, indicating an incompatible or incorrectly installed option board. The Drive cannot identify or communicate with the attached board, leading to system errors.

Complete Troubleshooting Guide

  1. 1

    Remove any option boards from the Drive.

  2. 2

    Cycle power to the Drive.

  3. 3

    Perform a factory initialization.

  4. 4

    Replace the option board with a compatible one, or replace the control board if the option board is known to be correct.