Acceleration Fault
Yaskawa · F7 Drive
What does Er - 09 mean?
This fault occurs during rotational Auto-Tuning if the motor fails to accelerate within the specified time (C1-01 + 10 seconds). It suggests insufficient torque, an excessive mechanical load, or incorrect acceleration parameters preventing the motor from reaching its target speed during the tuning sequence. Failure to accelerate properly will prevent accurate motor parameter identification.
Complete Troubleshooting Guide
- 1
Increase the acceleration time (C1-01) in the Drive parameters to allow more time for the motor to reach the target speed during tuning.
- 2
If torque limits (L7-01 for Forward Torque, L7-02 for Reverse Torque) are active and low, increase their values to provide sufficient torque.
- 3
If the motor is connected to a mechanical load, disconnect it and attempt rotational Auto-Tuning again without the load.