EF
FWD/REV Run Command Input Error
Yaskawa · GA500 Maintenance and Troubleshooting
What does EF mean?
This minor fault occurs when both a forward and a reverse run command are simultaneously active for more than 0.5 seconds, indicating a conflict in control signals. The motor will ramp to stop, preventing potential mechanical damage from conflicting commands.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Modify the control system to ensure that forward and reverse commands cannot be active simultaneously for an extended period (> 0.5s).
Source: Yaskawa GA500 Maintenance and Troubleshooting
View Official PDF