oL3

Overtorque Detection 1

Yaskawa · P1000 AC Drive

What does oL3 mean?

The drive detected that the motor torque has exceeded a preset overtorque threshold. This indicates a mechanical issue, excessive load, or incorrect parameter settings.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify Yaskawa P1000 parameters L7-01 (Current Limit Setting), E1-01 (Motor Rated Current), E2-01 (Motor Overload Protection Level), and acceleration/deceleration times (C1-xx) against motor nameplate data and application requirements.

  2. 2

    Inspect the mechanical system for binding, obstructions, excessive friction, or seized bearings in the motor and driven equipment.

  3. 3

    Check all motor power cable connections at both the drive and motor terminals for tightness and integrity.

  4. 4

    Measure the motor winding resistance between phases (U-V, V-W, W-U) and compare for balance; perform an insulation resistance test to ground if possible.

Browse all codes in this manual (60)