dWF1

EEPROM Memory DWEZ Data Error

Yaskawa · V1000 AC Drive

What does dWF1 mean?

This fault indicates an error in the drive's EEPROM peripheral circuit or a problem with the EEPROM data itself, often stemming from a corrupted DriveWorksEZ program saved to the EEPROM. This issue affects the drive's ability to retain critical program data and configuration. If unresolved, the drive will fail to operate correctly or maintain its programmed parameters.

Complete Troubleshooting Guide

  1. 1

    Re-energize the drive to attempt a reset.

  2. 2

    Initialize the drive parameters by setting A1-03 to 2220 or 3330, then re-upload the DriveWorksEZ project.

  3. 3

    If the fault persists after initialization, replace the control board or the entire drive unit.