EFO

Option External Fault (CP-916)

Yaskawa · VS-616G5 Variable Speed Drive

What does EFO mean?

This fault occurs when an external fault condition is detected via the CP-916 option card, specifically when the inverter is configured for serial communication using this card. The trip condition (open or closed) is defined by parameter F9-01. This signifies that an external safety or process interlock, monitored by the CP-916, has been triggered, requiring immediate attention.

Complete Troubleshooting Guide

  1. 1

    Identify the external device or input connected to the CP-916 option card that is triggering the fault.

  2. 2

    Verify the state of the external input based on parameter F9-01 (0=closed, 1=open for trip).

  3. 3

    Inspect wiring between the CP-916 option card and the external fault source for integrity.

  4. 4

    Check for issues with the CP-916 card itself, such as loose connection or internal fault.

  5. 5

    Ensure external fault detection (F9-02) is configured correctly, considering if detection should occur only when running or always.