PL Load parameter default values
Bosch Rexroth · IndraDrive MPx02
What does F2009 mean?
This non-fatal error signifies that a command to load default parameter values has been initiated or executed on the IndraDrive MPx02, typically indicated by 'PL' in the display. While not a fault in itself, it signals a significant change in drive configuration, potentially overriding custom settings.
Common Causes
- Manual command to load default parameters via HMI or software.
- Automatic loading of default parameters due to detection of corrupt or invalid stored parameters.
- Firmware update that required a parameter reset to defaults.
- Improper storage of non-volatile parameters, forcing the drive to revert to defaults.
- Initial startup of a new or factory-reset IndraDrive MPx02.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Confirm whether loading default parameters was an intentional action. If so, re-commission the drive with the correct application-specific parameters.
- 2
If unintentional, check the parameter history or event log to determine why the defaults were loaded.
- 3
Reload a previously saved, application-specific parameter set to restore the drive's custom configuration.
- 4
Verify the integrity of the drive's non-volatile memory or storage medium (e.g., MMC) to prevent future data loss.
- 5
Perform a full drive configuration backup after correctly setting all parameters.