F2110

Error in non-cyclical data communication of power section

Bosch Rexroth · IndraDrive MPx02

What does F2110 mean?

A fault occurred during non-cyclical data communication within the power section of the drive. This indicates an issue with data exchange that is not part of the regular control loop, potentially affecting configuration, diagnostics, or parameter updates. This can lead to improper power stage operation or failure to respond to commands.

Common Causes

  • Communication bus interference or noise
  • Defective communication hardware in the power section
  • Firmware issues affecting data exchange
  • Incorrect communication parameters
  • Temporary loss of internal communication link

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure and verify the control voltage supply (e.g., 24VDC) to the IndraDrive MPx02's control unit, ensuring it is stable and within specifications.

  2. 2

    Inspect all internal ribbon cables and plug-in connections between the control unit and the power module of the drive for secure seating, signs of damage, or corrosion.

  3. 3

    Verify the drive's operating parameters, particularly those related to the power section configuration and communication settings, against the machine's latest configuration backup.

  4. 4

    Measure the DC bus voltage within the drive's power section and confirm it is stable and within the specified operating range as per the drive's technical documentation.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026