F3115

Error, brake check time interval exceeded

Bosch Rexroth · IndraDrive MPx02

What does F3115 mean?

The allowed time interval for performing a brake check has been exceeded. Safety-related brake checks are periodic tests to verify the holding brake's functionality. Failure to complete this check within the configured interval indicates either a brake malfunction, a system delay, or an issue preventing the check's execution, compromising holding safety.

Common Causes

  • Brake check not initiated within the required time frame
  • Brake check duration exceeded due to brake malfunction
  • System delays preventing timely execution of the brake check
  • Incorrect parameter for brake check interval or duration
  • Encoder fault preventing accurate position feedback during check

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify drive parameters related to brake check interval and safety brake control (e.g., P-055x, P-060x series for IndraDrive) against the original commissioning documentation.

  2. 2

    Inspect the motor brake power cabling and signal connections for damage, proper seating, and continuity between the IndraDrive and the motor.

  3. 3

    Measure the actual voltage supplied to the motor holding brake during the check cycle and compare it to the specified nominal voltage for the brake.

  4. 4

    Verify the integrity and signal quality of the motor encoder feedback system, as incorrect position data can interfere with the brake check sequence.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026