F7031

Incorrect direction of motion

Bosch Rexroth · IndraDrive MPx02

What does F7031 mean?

This safety technology error indicates that the IndraDrive MPx02 has detected motion in an incorrect or unintended direction, violating a safety-related directional monitoring function. This could be due to a control error or external influence, leading to an immediate safety stop.

Common Causes

  • Incorrect parameterization of safety-related direction monitoring (e.g., S-0-0102 'Safe direction').
  • Programming error in the motion controller causing a command for the wrong direction.
  • Motor phase reversal or encoder wiring issue, causing actual motion to be opposite of commanded.
  • Mechanical system defect (e.g., backlash, broken gear) leading to unintended direction of movement.
  • Encoder fault providing inverted or incorrect direction feedback.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Review and adjust the safety-related direction monitoring parameter (e.g., S-0-0102) in the IndraDrive MPx02 to ensure it aligns with the intended safe directions of motion.

  2. 2

    Verify the motion program in the master controller or PLC, ensuring correct direction commands are issued.

  3. 3

    Check the motor phasing and encoder wiring for correct connections. If necessary, reverse motor phases (U, V, W) or encoder direction parameter (S-0-0130 'Encoder direction of rotation').

  4. 4

    Inspect the mechanical system for excessive backlash, loose couplings, or other defects that could cause unintended reversal.

  5. 5

    Verify the motor encoder for correct direction sensing, checking for potential noise or signal issues.

Browse all codes in this manual (99)
Verified technical data. Last updated: March 2026

Related Faults

Source: Bosch Rexroth IndraDrive MPx02