Übersetzen...
502

Overcurrent on DC side (PV1)

Fronius · Primo GEN24

Was bedeutet 502 ?

The Fronius Primo GEN24 208-240 inverter has detected an excessive current flowing from the PV1 string on the DC side. This indicates a potential short circuit within the PV1 array or an incorrect string configuration.

Häufige Ursachen

  • Overcurrent on the DC side (PV1).
  • Short circuit on the PV array.
  • Incorrect PV array sizing or configuration.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Disconnect the PV1 string using the DC disconnector and inspect all PV modules, wiring, and connectors for signs of damage or short circuits.

  2. 2

    Measure the open-circuit voltage (Voc) and short-circuit current (Isc) of the PV1 string and compare them against expected values based on module specifications.

  3. 3

    Verify that the PV1 string configuration (number of modules in series and parallel) is within the Fronius Primo GEN24 208-240 inverter's maximum current limits.

  4. 4

    Check for any external DC combiner box or array wiring that might be causing a short circuit condition.

  5. 5

    If all external checks pass, the issue may be internal to the inverter; contact Fronius service.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes