ABB · ACS580
An internal fault indicating an overflow related to an internal text file within the drive's memory. This is usually indicative of a software bug or a transient memory allocation issue. Continued occurrence can compromise drive stability.
Click steps to track your progress.
Perform a drive power cycle to clear transient memory states.
If custom text files are used, verify their size against drive specifications and reduce content if necessary.
Perform a parameter reset to factory defaults (P96-01=1) and then reconfigure the drive.
Update the drive's main firmware to the latest stable release to address potential software bugs.
If the fault recurs frequently after these steps, consider replacing the main control board due to a potential memory hardware issue.