ABB · ACS580
A short circuit has been detected within the brake chopper circuit, specifically occurring when an earth fault condition is also present and the brake chopper is active. This is a severe fault that can lead to rapid destruction of the brake chopper power components and poses a safety risk due to high current flow.
Click steps to track your progress.
De-energize the drive. Disconnect the brake resistor connections (e.g., terminals R+, R- or B+, B-).
Measure resistance across the brake resistor terminals; verify it matches the specified resistance (e.g., 20 ohms, 50 ohms).
Measure insulation resistance from each brake resistor terminal to ground (PE) using a megohmmeter (500V).
Measure continuity between the drive's internal brake chopper terminals (e.g., DC+ to BRK, DC- to BRK) to check for internal shorts (expect open circuit when not switching).
Inspect the brake chopper module for visible damage, scorch marks, or loose connections.