ABB · ACS580
An analog input signal has gone outside the predefined minimum or maximum limits. This fault is programmable and prevents the drive from operating with out-of-range sensor feedback, which could lead to incorrect control, erratic behavior, or damage to connected equipment.
Click steps to track your progress.
1. Measure the actual analog signal voltage or current at the drive's analog input terminals (e.g., AI1 and AGND) using a multimeter.
2. Inspect the wiring connection from the external sensor to the drive's analog input terminals (e.g., AI1, AGND). Ensure connections are tight and intact.
3. Test the external sensor directly by simulating its expected operating range or applying known physical inputs to verify its output signal.
4. Verify parameters P10.05 (AI1 Min Supervision Limit) and P10.06 (AI1 Max Supervision Limit) are correctly configured for the expected signal range of the sensor.
5. Check for proper shielding and grounding of the analog input cable to minimize electrical noise interference, especially if the cable runs parallel to power lines.