ABB · ACS580
An external device configured as External Event 2 (parameters 31.03 and 31.04) has generated a fault. This indicates a problem with equipment or sensors outside the drive's direct control, potentially impacting the entire system's operation and requiring immediate attention.
Click steps to track your progress.
1. Identify the digital input terminal (e.g., DI3, DI4) configured as External Event 2 in P31.04 (DI Config).
2. Measure the voltage at the identified digital input terminal relative to common (e.g., 24VDC or 0VDC) to confirm its current state.
3. Inspect the external device (e.g., limit switch, pressure switch) connected to this input for proper operation and reset if tripped.
4. Verify the integrity of the wiring from the external device to the drive's digital input terminal, checking for opens or shorts using a multimeter.
5. Review P31.04 (DI Config) to ensure the input polarity (e.g., Normally Open or Normally Closed) is correctly configured for the external device.