ABB · ACS580
The temperature of the brake resistor has exceeded its configured warning limit (parameter 43.12). Continuous operation under this condition will lead to premature failure of the resistor and inability to dissipate regenerative energy, risking DC link overvoltage.
Click steps to track your progress.
1. Verify the brake resistor's physical installation for proper ventilation and airflow, ensuring no obstructions or excessive dust buildup.
2. Measure the resistance of the brake resistor using an ohmmeter to confirm it matches the nominal value set in P43.01.
3. Confirm the brake resistor's continuous power rating and duty cycle are suitable for the application's braking demands, comparing with P43.02.
4. Increase the deceleration time (P21.02) to reduce the rate of regenerative energy flow into the brake resistor, if the application allows.
5. Monitor the actual brake resistor temperature (if a sensor is present and accessible) and compare it to the warning limit set in P43.12.
6. Consider installing a brake resistor with a higher continuous power rating or a larger heat sink if frequent braking is unavoidable.