ABB · ACS580
The Insulated Gate Bipolar Transistor (IGBT) within the brake chopper has exceeded its internal temperature warning limit. This indicates excessive heat generation due to sustained braking, inadequate cooling, or an overdriven chopper, risking damage to the power components and potentially causing drive failure.
Click steps to track your progress.
1. Check the drive's cooling fan operation and ensure the heatsink fins are free from dust and debris, allowing for proper airflow.
2. Measure the ambient temperature immediately surrounding the drive and within the control cabinet to ensure it is within specified operating limits.
3. Increase the deceleration time (P21.02) if the application allows, to reduce the frequency and intensity of regenerative braking.
4. Monitor the drive's internal temperature readings (e.g., P06.18, P06.19 for module temperatures) to observe trends and identify specific hot spots.
5. Verify that the drive enclosure has adequate ventilation, and consider adding exhaust fans or an air conditioner if high ambient temperatures persist.