ABB · ACS580
An external device configured as External Event 5 (parameters 31.09 and 31.10) has generated a warning. This indicates a potential issue with external equipment or sensors that should be investigated, though it may not cause an immediate drive trip. Addressing warnings proactively prevents escalation to faults.
Click steps to track your progress.
1. Identify the external device or process monitoring sensor connected to the digital input specified by P31.09 (External Event 5 source).
2. Measure the voltage level at the drive's digital input terminal corresponding to the external warning to confirm its state.
3. Investigate the external equipment or process for the specific condition that would trigger External Event 5 (e.g., fluid levels, mechanical positions, auxiliary motor status).
4. Confirm P31.09 (External Event 5 source) and P31.10 (External Event 5 action) are correctly configured for the intended external signal and warning response.
5. Inspect and clean the contacts of any external relays or switches that generate the warning signal, ensuring solid electrical connections.