An asymmetric loss of one of the Safe Torque Off (STO) signals has occurred (e.g., IN2 lost while IN1 is present). This is interpreted as a malfunction in the safety circuit and causes the drive to trip. The drive will not start until both STO signals are restored and all related faults are reset.
Click steps to track your progress.
De-energize the drive. Measure continuity of the STO IN2 cable conductor from the safety source (relay/PLC) to the drive's STO IN2 terminal.
Measure voltage across the STO IN2 terminal (e.g., X2) relative to common (e.g., X3) with the safety function engaged; expect 24VDC.
Verify the output status of the safety relay or PLC module driving STO IN2, ensuring it provides a consistent signal when active.
Inspect the wiring at the drive's STO IN2 terminal (e.g., X2) for loose connections, damage, or corrosion.
If a separate safety module is used, check its diagnostic LEDs or software status for faults related to STO channel 2.