EL
ErrorLib
Brands
||
  1. Home
  2. ABB
  3. ACS880-07 Hardware

ABB ACS880-07 Hardware

2 fault codes documented

ALARM 1

Ground Fault Alarm (Drive Trip)

This alarm signal from the ground fault monitor (option +Q954) is explicitly recommended to be connected for immediate drive tripping upon detection of a ground fault in IT (ungrounded) systems. The contact is normally closed when no ground fault is present and has a load capacity of 250 V AC, 2 A. Be aware that the ground fault monitor performs self-testing, which might momentarily activate this signal, necessitating careful distinction between actual faults and test sequences.

ALARM 2

Ground Fault Alarm (Signal Output)

This alarm signal from the ground fault monitor (option +Q954) is intended for general alarm indication purposes, rather than directly tripping the drive. The contact is normally closed when no ground fault is present and has a higher load capacity of 250 V AC, 8 A. It is crucial to understand that the monitor's internal self-testing might briefly activate this signal, requiring careful interpretation by any receiving alarm or monitoring system.

About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.