ABB · ACS880-07 Hardware
This alarm signal from the ground fault monitor (option +Q954) is explicitly recommended to be connected for immediate drive tripping upon detection of a ground fault in IT (ungrounded) systems. The contact is normally closed when no ground fault is present and has a load capacity of 250 V AC, 2 A. Be aware that the ground fault monitor performs self-testing, which might momentarily activate this signal, necessitating careful distinction between actual faults and test sequences.
Click steps to track your progress.
De-energize and lock out power to the drive. Verify zero voltage at input terminals L1, L2, L3 and output terminals T1, T2, T3 using a CAT III rated multimeter.
Disconnect all motor phase conductors (U, V, W) from the drive output terminals. Measure insulation resistance between each motor phase and the motor frame ground (PE) using a megohmmeter (e.g., 1000V DC test voltage). A reading below 1 Megohm indicates a motor or cable fault.
Measure insulation resistance between each drive output phase (T1, T2, T3) and the drive chassis ground (PE) with motor disconnected. A reading below 1 Megohm suggests an internal drive fault.
Inspect the ground fault monitor (+Q954) connection terminals X1:1 and X1:2 for secure wiring and proper contact.
Verify drive parameter P3-10 (Ground Fault Trip Level) is set appropriately for the IT system and does not trigger prematurely due to normal capacitive leakage.
Visually inspect the drive's power section (IGBTs, rectifiers, busbars) for signs of arcing, discoloration, or component damage indicative of a short to ground.