EL
ErrorLib
Brands
||
  1. Home
  2. ABB
  3. ACS880-07 Hardware
  4. ALARM 2
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

ALARM 2

Ground Fault Alarm (Signal Output)

ABB · ACS880-07 Hardware

What does ALARM 2 mean?

This alarm signal from the ground fault monitor (option +Q954) is intended for general alarm indication purposes, rather than directly tripping the drive. The contact is normally closed when no ground fault is present and has a higher load capacity of 250 V AC, 8 A. It is crucial to understand that the monitor's internal self-testing might briefly activate this signal, requiring careful interpretation by any receiving alarm or monitoring system.

Common Causes

  • Developing insulation degradation in motor windings or cables, leading to increased leakage current that exceeds the alarm threshold but not the trip threshold.
  • Accumulation of moisture or conductive dust on motor terminals, connection blocks, or within the motor itself, creating an intermittent or high-resistance ground path.
  • External electromagnetic interference (EMI) affecting the ground fault monitor (+Q954) sensing circuit, causing a false alarm signal without an actual ground fault.
  • Parameter P3-11 (Ground Fault Alarm Level) is set too low, making the system overly sensitive to normal operational leakage currents.
  • Fluctuations in supply voltage or load conditions causing temporary increases in capacitive leakage current through aging insulation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the wiring connections for the ground fault monitor's alarm output at terminals X1:3 and X1:4 for integrity and absence of loose strands or corrosion.

  2. 2

    Monitor the ground leakage current using a clamp-on ground leakage current meter around the main power cable's ground conductor (PE) during drive operation under varying loads.

  3. 3

    Perform an insulation resistance test (megger test) on motor windings and cables (U, V, W to PE) to identify any areas with insulation degradation (readings between 1 MOhm and 5 MOhm may indicate early warning).

  4. 4

    Verify the drive parameter P3-11 (Ground Fault Alarm Level) is configured correctly according to system specifications and the expected capacitive leakage in the IT system.

  5. 5

    Check for potential sources of EMI (e.g., contactors, switching power supplies) near the ground fault monitor or its current transformer (CT) that might induce false alarm signals.

  6. 6

    If intermittent, consider trending insulation resistance over time using an insulation monitoring device to detect gradual degradation that may not be apparent during a single spot test.

Browse all codes in this manual (2)
Verified technical data. Last updated: April 2026

Related Faults

ALARM 1Ground Fault Alarm (Drive Trip)
Source: ABB ACS880-07 Hardware
View Official PDFSearch more codes in this manual