ACS880 · Spinning and Traverse Control Program Firmware
The drive tripped because the motor did not stop within the maximum allowed time for an emergency stop (mode Off3). This time is defined by parameter 31.33 (Emergency ramp supervision delay). When this fault occurs, bit 8 of parameter 06.17 (Drive status word 2) is set, and the drive coasts to a stop.
Click steps to track your progress.
Verify the mechanical load and inertia of the application to ensure it can decelerate within the configured emergency ramp time.
Check the setting of parameter 31.33 (Emergency ramp supervision delay) and increase it if necessary to allow sufficient time for mechanical stopping.
Inspect the motor and mechanical system for any binding, friction, or external forces that could impede deceleration.
If an external braking system or dynamic braking is utilized, verify its functionality and proper operation.
Ensure parameter 31.32 (Emergency ramp supervision) is correctly configured according to the application's emergency stop requirements.