A782

FEN temperature

ACS880 · Spinning and Traverse Control Program Firmware

What does A782 mean?

An error in temperature measurement has been detected when a KTY or PTC temperature sensor is connected to an FEN-xx encoder interface. Specifically, the FEN-01 interface module does not support KTY sensors, which would trigger this warning if incorrectly configured. This indicates a mismatch between sensor type, encoder interface settings, or module activation.

Common Causes

  • An incorrect temperature sensor type (e.g., KTY sensor) is connected to an incompatible FEN-xx encoder interface module (e.g., FEN-01).
  • Parameter 35.11 (Temperature 1 source) or 35.21 (Temperature 2 source) is incorrectly set for the actual encoder interface and sensor installation.
  • Incorrect configuration in parameters 91.21 and 91.24, which are related to encoder module settings.
  • The corresponding encoder interface module (activated via parameters 91.11 through 91.14) is not properly enabled or recognized.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the type of temperature sensor (KTY or PTC) connected to the FEN-xx encoder interface. Ensure that if FEN-01 is used, a PTC sensor is connected.

  2. 2

    Check parameters 35.11 (Temperature 1 source) and 35.21 (Temperature 2 source) to confirm they are correctly configured for the installed encoder interface and sensor type.

  3. 3

    Review parameters 91.21 and 91.24 to ensure their settings align with the installed encoder interface module configuration.

  4. 4

    Ensure that the specific encoder interface module receiving the temperature input is correctly activated in parameters 91.11 to 91.14.

  5. 5

    After making any parameter changes, use parameter 91.10 (Encoder parameter refresh) to validate the new settings and clear the warning.

Browse all codes in this manual (21)
Verified technical data. Last updated: April 2026

Related Faults

6683EFB invalid parameterization6684EFB load fault6881Text data overflow
Source: ACS880 Spinning and Traverse Control Program Firmware
Open Manual (Page 560)Search more codes in this manual