An error in temperature measurement has been detected when a KTY or PTC temperature sensor is connected to an FEN-xx encoder interface. Specifically, the FEN-01 interface module does not support KTY sensors, which would trigger this warning if incorrectly configured. This indicates a mismatch between sensor type, encoder interface settings, or module activation.
Click steps to track your progress.
Verify the type of temperature sensor (KTY or PTC) connected to the FEN-xx encoder interface. Ensure that if FEN-01 is used, a PTC sensor is connected.
Check parameters 35.11 (Temperature 1 source) and 35.21 (Temperature 2 source) to confirm they are correctly configured for the installed encoder interface and sensor type.
Review parameters 91.21 and 91.24 to ensure their settings align with the installed encoder interface module configuration.
Ensure that the specific encoder interface module receiving the temperature input is correctly activated in parameters 91.11 to 91.14.
After making any parameter changes, use parameter 91.10 (Encoder parameter refresh) to validate the new settings and clear the warning.