The power supply on the U-phase gate driver board has failed. This affects the control of the U-phase output and can lead to motor malfunction or drive damage.
Click steps to track your progress.
1. Power down the drive and check the DC voltage output of the U-phase gate driver board's local power supply for Port 2 (typically 15VDC or 18VDC) at specified test points.
2. Perform a thorough visual inspection of the U-phase gate driver board (Port 2) for any obvious physical damage, discolored components, or cold solder joints.
3. Isolate and measure the resistance values of the U-phase IGBT gate-emitter terminals on Port 2 (drive powered off, DC bus discharged) to identify potential shorts or open circuits.
4. Verify all internal wiring and ribbon cable connections to the U-phase gate driver board for Port 2 are firmly seated and free from damage or corrosion.
5. If external cooling fans or heat sinks are present on the U-phase output stage, ensure they are clean and functioning correctly to prevent thermal stress on components.