Allen-Bradley · PowerFlex 750
This fault is asserted when the DC bus voltage drops to 80% of its rated value on port 3. This indicates a significant loss of DC bus voltage which can lead to drive shutdown and loss of control.
Click steps to track your progress.
Measure the 3-phase AC input voltage at terminals R, S, T (Port 3) to confirm nominal values are present and stable.
Check the status of all upstream circuit breakers and fuses supplying power to the Port 3 input.
Monitor the actual motor current (e.g., Parameter P3-01 for Port 3) to verify it is within the drive's rated limits.
Inspect the DC link capacitors on Port 3 for physical signs of damage, such as bulging, leaking electrolyte, or discoloration.
Using a multimeter, measure the DC bus voltage across the P+ and N- terminals (Port 3) and compare it to the value displayed on the drive.