EL
ErrorLib
Brands
||
  1. Home
  2. Allen-Bradley
  3. PowerFlex 750
  4. 11119
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

11119

P1 240 V AC Loss

Allen-Bradley · PowerFlex 750

What does 11119 mean?

240V AC input power was lost on port 1 while the drive was in an active state (e.g., MCS opening, closing, or closed). This causes the drive to cease operation.

Common Causes

  • Tripped upstream circuit breaker or blown fuse on the 240V AC input line for Port 1.
  • Loose or corroded wiring connection at the drive's 240V AC input terminals (L1/L2) for Port 1.
  • Failure of an auxiliary control transformer or power supply providing 240V AC to the drive's control section (Port 1).
  • Intermittent power supply to the drive's control section (Port 1) due to contactor chatter or faulty relay.
  • Faulty 240V AC input voltage sensing circuit or its associated wiring for Port 1.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the status of all upstream circuit breakers and fuses protecting the 240V AC input to Port 1.

  2. 2

    Measure the 240V AC voltage at the drive's L1 and L2 input terminals (Port 1) using a multimeter.

  3. 3

    Inspect and tighten all power wiring connections at the 240V AC input terminals (Port 1) for looseness or damage.

  4. 4

    Check the output voltage of any control transformer supplying 240V AC power to the drive (Port 1), if applicable.

  5. 5

    Confirm the proper operation of input contactors or relays that supply 240V AC power to Port 1.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

100Parameter Chksum101PwrDn NVS Blank10132I1 Incompat PS
Source: Allen-Bradley PowerFlex 750
View Official PDFSearch more codes in this manual