11120

P1 240V AC Discon

Allen-Bradley · PowerFlex 750

What does 11120 mean?

The 240V AC disconnect switch on port 1 is open when the precharge controller is in the ready state, but the molded case switch (MCS) is not closed. This prevents the drive from starting or operating.

Common Causes

  • The main 240V AC disconnect switch (Port 1) is physically open or improperly closed.
  • Failure of the auxiliary contact on the disconnect switch (Port 1) to provide closure feedback to the controller.
  • Broken or loose wiring connecting the disconnect switch auxiliary contact (Port 1) to the drive's input status terminals.
  • Faulty input status monitoring circuit on the drive control board (Port 1) for the disconnect switch.
  • Incorrect drive parameter setting (e.g., Parameter P1-03 for Port 1) expecting a closed disconnect when it's open.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Physically confirm the 240V AC disconnect switch (Port 1) handle is fully in the CLOSED position.

  2. 2

    Measure continuity across the auxiliary contacts (e.g., terminals 13/14) of the 240V AC disconnect switch (Port 1) when closed.

  3. 3

    Trace and inspect the wiring from the disconnect switch auxiliary contacts (Port 1) to the drive's digital input terminals (e.g., DI1, DI2).

  4. 4

    Verify the status of the corresponding digital input (e.g., Digital Input 1 status) on the drive's display for Port 1.

  5. 5

    Check drive parameters (e.g., Parameter P1-03, 'Disconnect Input Selection' for Port 1) to ensure correct configuration for the disconnect input.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026