Allen-Bradley · PowerFlex 750
The 240V AC disconnect switch on port 2 is open when the precharge controller is in the ready state, but the molded case switch (MCS) is not closed. This prevents the drive from starting or operating.
Click steps to track your progress.
Physically confirm the 240V AC disconnect switch (Port 2) handle is fully in the CLOSED position.
Measure continuity across the auxiliary contacts (e.g., terminals 13/14) of the 240V AC disconnect switch (Port 2) when closed.
Trace and inspect the wiring from the disconnect switch auxiliary contacts (Port 2) to the drive's digital input terminals (e.g., DI1, DI2).
Verify the status of the corresponding digital input (e.g., Digital Input 1 status) on the drive's display for Port 2.
Check drive parameters (e.g., Parameter P1-03, 'Disconnect Input Selection' for Port 2) to ensure correct configuration for the disconnect input.