EL
ErrorLib
Brands
||
  1. Home
  2. Allen-Bradley
  3. PowerFlex 750
  4. 113
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

113

Tracking DataErr

Allen-Bradley · PowerFlex 750

What does 113 mean?

An internal data error affecting tracking data has occurred. This is a generic data integrity issue, potentially compromising the drive's ability to store or retrieve critical operational tracking information. Such errors can lead to unpredictable drive behavior or loss of diagnostic capabilities if left unresolved.

Common Causes

  • Corruption of internal drive tracking data due to power fluctuations or electromagnetic interference (EMI).
  • Sudden power loss or brownout during a write operation to tracking data memory in non-volatile storage (NVS).
  • Internal non-volatile memory (NVS) hardware fault on the main control board (MCB).
  • Firmware bug related to tracking data management and storage routines.
  • Repeated write cycles to the same NVS sector leading to memory wear and data integrity issues.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Perform a full parameter reset to factory defaults (e.g., P0-01 to "Factory Reset") to clear potentially corrupted tracking data.

  2. 2

    2. Upload saved parameters from a reliable backup file to restore a known good configuration.

  3. 3

    3. Verify the stability of the incoming AC line voltage (e.g., 480V L1-L2-L3) and control power (e.g., 24VDC) for the drive.

  4. 4

    4. Check for and install any available firmware updates for the main control board (MCB) that may address data integrity issues.

  5. 5

    5. If the fault persists, the main control board (MCB) likely has a damaged non-volatile storage module and requires replacement.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

100Parameter Chksum101PwrDn NVS Blank10132I1 Incompat PS
Source: Allen-Bradley PowerFlex 750
View Official PDFSearch more codes in this manual