EL
ErrorLib
Brands
||
  1. Home
  2. Allen-Bradley
  3. PowerFlex 750
  4. 11315
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

11315

P3 Bus Dip

Allen-Bradley · PowerFlex 750

What does 11315 mean?

The DC bus voltage on port 3 has dipped more than 180V below the drive's bus memory when the drive is offline or in stand-alone mode. This indicates an unstable DC bus voltage, which can affect drive reliability.

Common Causes

  • Transient voltage sag in the incoming AC line voltage (Port 3) from the utility grid or plant distribution system.
  • Intermittent connection or high resistance at the main input power terminals (R, S, T) for Port 3, causing voltage drops.
  • Degradation or failure of DC link capacitors (Port 3), leading to a loss of capacitance and inability to buffer voltage dips.
  • Abnormal regenerative energy feedback from an external braking resistor or motor (Port 3) causing bus voltage instability.
  • Faulty DC bus voltage sensor or its associated signal conditioning circuit (Port 3) providing an incorrect reading.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Use a power quality analyzer to monitor the 3-phase AC input voltage (Port 3) for sags or momentary interruptions.

  2. 2

    Inspect and tighten all input power wiring connections at the drive's L1, L2, L3 terminals (Port 3) and upstream devices.

  3. 3

    Inspect DC link capacitors (Port 3) for physical defects like bulging, leaking electrolyte, or discoloration.

  4. 4

    Verify the integrity and correct connection of any external braking resistors or regenerative units associated with Port 3.

  5. 5

    Measure the actual DC bus voltage across the P+ and N- terminals (Port 3) with a multimeter to verify the controller's displayed value.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

100Parameter Chksum101PwrDn NVS Blank10132I1 Incompat PS
Source: Allen-Bradley PowerFlex 750
View Official PDFSearch more codes in this manual