Allen-Bradley · PowerFlex 750
The drive has repeatedly attempted to automatically reset a fault and resume operation but has failed to clear the underlying condition within the programmed number of tries (P348 [Auto Rstrt Tries]). This indicates a persistent problem that the drive cannot self-correct, leaving it in a stopped state. Manual intervention is required to diagnose and fix the root cause of the original fault.
Click steps to track your progress.
1. Identify the *preceding* fault code from the drive's fault history (e.g., 'A1-00' for last fault) that triggered the auto-restart attempts.
2. Reset the drive manually to clear the 'AuRsts Exhausted' fault and observe for the recurrence of the primary fault.
3. Investigate and troubleshoot the primary fault code according to its specific causes and fix steps.
4. Temporarily disable auto-restart (P347 = 0) to prevent repeated, unsuccessful attempts and allow for focused troubleshooting.
5. If auto-restart is required, consider increasing P348 (Auto Rstrt Tries) or P349 (Auto Rstrt Delay) only after addressing the primary fault's root cause.