44

Phase UNegToGrnd

Allen-Bradley · PowerFlex 750

What does 44 mean?

A phase-to-ground fault has been detected between the drive and the motor on output phase U, specifically identifying a negative voltage transient or specific ground path. This indicates insulation breakdown or a short from output phase U to earth. This condition can damage the drive and motor if not quickly addressed, and poses an electrical safety risk.

Common Causes

  • Insulation breakdown of the motor winding for phase U to the motor frame (ground), often due to moisture ingress, aging, or localized damage.
  • Damage to the motor cable insulation for conductor U, creating a direct path to conduit, cable tray, or cabinet ground.
  • Water ingress or condensation inside the motor terminal box, bridging phase U to the grounded enclosure.
  • Improper or compromised grounding of the motor frame or cable shielding, leading to an unintended low-impedance ground path for phase U.
  • Arcing, carbon tracking, or conductive debris from phase U to ground within the motor, drive output wiring compartment, or intermediate junction boxes.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Disconnect all motor power cables from drive output terminals U, V, W and disconnect motor frame ground (PE).

  2. 2

    2. Perform an insulation resistance test (Megger) between motor terminal U and motor frame ground (PE) at 500VDC for 60 seconds (expected reading: >1 MOhm).

  3. 3

    3. Inspect the motor cable for conductor U for physical damage to the outer jacket and internal insulation, especially at bends or points of stress to any grounded surface.

  4. 4

    4. Check the motor terminal box for signs of moisture, conductive dust, loose wire strands, or corrosion bridging phase U to the grounded enclosure.

  5. 5

    5. Verify the integrity of the motor frame ground connection, ensuring continuity to the protective earth (PE) busbar with an ohmmeter (expected <0.1 Ohm).

  6. 6

    6. If motor and cable test good, measure insulation resistance between drive output terminal U and drive ground (PE) with a Megger (drive powered off, DC bus discharged) to check for an internal drive fault.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026