Beckhoff · TwinCAT 2 NC
During the initial system start-up, the set position could not be successfully initialized for all trials (with/without overflow/underflow) within the final position minimum and maximum limits. This means the axis could not establish a valid initial position, preventing it from becoming referenced and ready for motion.
Click steps to track your progress.
1. Verify the functionality of the homing switch (e.g., by manually activating it) and check its input status via diagnostic D-07.
2. Review and adjust the homing offset parameter (P4-05) to ensure the axis initializes within the absolute position limits (P3-04, P3-05).
3. Check the encoder signal quality (e.g., A/B phase signals on X3-1, X3-2) with an oscilloscope for noise or dropouts during axis movement.
4. Expand the configured absolute position limits (P3-04, P3-05) slightly to provide more tolerance during the initial position setting.
5. Inspect the mechanical coupling between the motor and the load for any play or slippage that could affect homing repeatability.